MODBUS Damatic RTU

MODBUS Damatic RTU

Valmet Damatic MODBUS RTU communication protocol

Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions

Supported device types and versions


MODBUS protocol, version RTU, supports data reading from a control system Valmet Damatic by means of gateway RTU GTW:LIS.

Communication line configuration


  • Communication line category: Serial.

  • Parameters of asynchronous line depending on the design and type of device connection – literature "Overview of the Damatic XD System – VALMET Automation V.5.4 rev.7".

Communication station configuration


  • Communication protocol: Valmet MODBUS RTU GTW:LIS.

  • Station address is a decimal number in the range of 0 to 255.


Station protocol parameters

There can be defined the following parameters:

Table 1

Key word

Full name

Meaning

Unit

Default value

RC

Retry Count

Number of retry calls when an error in communication occurs.

-

2

RT

Retry Timeout

Delay between retry calls if an error in communication occurs.

ms

300 millisec.

WFT

Wait First Timeout

First waiting on the response after sending a call.

ms

200 millisec.

WT

Wait Timeout

Delay between the readings of a response until it is completed.

ms

100 millisec.

MWR

Max Wait Retry

Number of retry response reading until it is completed.

-

10

String with protocol parameters is written according to this rule:

Key_word=value;Key_word=value; ...

Example:

RC=1;RT=500;

If a key word with valid value has not been found in the initial string, default value is used according to Table 1.

I/O tag configuration


I/O tags: Ai, Di

Address – a decimal number in the range of 0 to 65535 – number of MODBUS register.

In general, 2 bytes are read (sign integer) from a particular register. For Ai points, IEE 754 standard can be used, which is a reading of 4 bytes in FLOAT, i.e. the registers on Address and Address+1.

For Di points, number of bit must be from the range of 0 to 15 – one bit from 16 bits from MODBUS register which was read.

Literature


-

Changes and modifications


-

Document revisions


  • Ver. 1.0 – February 9, 2000