OPC XML Data Access 1.01 Client

OPC XML Data Access 1.01 Client

OPC XML Data Access 1.01 Client communication protocol

Protocol specification
Communication line configuration
Protocol configuration on the communication station
I/O tag configuration
Literature
Changes and modifications
Document revisions

Protocol specification


Protocol OPC XML DA is a transitive protokolom between protocols OPC Data Access Client and OPC Unified Architecture Data Access Client.
An improvement to OPC Data Access Client is a transition to platform-independent communication (using XML data format and SOAP-Web Services over HTTP protocol).
The latest from OPC protocol family is the protocol OPC Unified Architecture Data Access Client which maintains platform independence and optimizes performance by replacing XML / SOAP communications with binary encoding and by eliminating HTTP protocol.

Communication line configuration


Communication line category: HTTP client
URL: URL address of OPC XML server in form http://host[:port][/path[?query]], e.g. http://172.16.0.1 or http://myopcserver.domain:8080/opcxml
Proxy: IP address or name of optional proxy server. If entered, KOM process will connect to proxy server instead of host listed in parameter URL.
User: optional name for authentication on proxy server (support for authentication has not been implemented).
Password: optional password for authentication on proxy server (support for authentication has not been implemented).

Protocol line parameters

Parameter

Meaning

Unit

Default value

Debug Responses Parsing

Enable debug messages at the OPC XML server response level.

YES/NO

NO

Debug Http I/O Data

Turn on debug messages at HTTP communication level.

YES/NO

YES

Debug Http Responses

Turn on debug messages with headers and body of HTTP response.

YES/NO

NO

Debug Received Values

Turn on debug messages with received values.

YES/NO

YES

Protocol configuration on the communication station


  • Communication protocol: OPC XML Data Access 1.01 Client.

  • Station address: unused.

Station protocol parameters

Table 1

Full name

Description

Default value

Request option ReturnErrorText

Parameter of Subscribe and Write requests. If set to YES, the server will return verbose error description.

NO

Request option ReturnDiagnosticInfo

Parameter of Subscribe and Write requests. If set to YES, the server will return verbose server specific diagnostic information to provide additional information relative to item specific errors.

NO

Request option ReturnItemTime

Parameter of Subscribe and Write requests. If set to YES, the server will return the timestamp for each Item.

YES

Request option ReturnItemPath

Parameter of Subscribe and Write requests. If set to YES, the server will return ItemPath (a path to Item within Namespace) for each Item.

NO

Request option ReturnItemName

Parameter of Subscribe and Write requests. If set to YES, the server will return ItemName (a fully qualified identifier of Item) for each Item.

NO

Request option ReturnValuesOnReply

Parameter of Subscribe and Write requests. If set to YES, the server will return values of all Items in reply to Subscribe and value of Item in reply to Write as if the client had performed a Read request directly after the Write request.

YES

I/O tag configuration


I/O tag configuration dialog window is used for setting the monitored objects.

Object address setting

Name

Meaning

Item Name

Unique text identifier of Data in OPC XML server.

Subscribe

If the setting is checked, the KOM process uses this Item in Subscribe request to query the value of the object.
This setting can be unchecked for objects that are not supposed to be read (e.g. write-only I/O tags or objects that have been removed from the communication).

Literature