Siemens SIMATIC S7 ISO on TCP

Siemens SIMATIC S7 ISO on TCP

Siemens SIMATIC S7 ISO on TCP communication protocol

Supported device types and versions
Communication line configuration
Line protocol parameters
Communication station configuration
I/O tag configuration
Note on Siemens TIA Portal version 12 and above
Note on Siemens S7 1200/1500
Literature
Changes and modifications
Document revisions

Supported device types and versions


This protocol supports a data reading/writing from the control PLC machines Siemens SIMATIC:

  • types S7-300 and S7-400 equipped by an ethernet interface for the communication S7 ISO over TCP.

  • types S7-1200, S7-1500

  • Siemens LOGO

  • Siemens Microbox

Note: communication via Profinet/Profibus adapter ACCON-NetLink-PRO compact produced by company DELTALOGIC has been verified. Communication with multiple S-300 series PLCs on Profibus worked after firmware upgrade of adapter to version V2.54 (31. march 2015) with adapter's BIOS version V2.39 (7. June 2011). When the adapter's firmware was version V2.37 (8.august 2011), communication could not be correctly established.
Note: communication with PLC Siemens LOGO was tested. A part of memory that is accessible for reading/writing is the V area that is seen as DB1.
Note: the protocol has a "big endian" data representation.

Communication line configuration


  • Communication line category: TCP/IP-TCP, TCP Redundant.

  • IP address (addresses) is set according to a network configuration of a specific Siemens SIMATIC device.

  • The port number is 102 (according to specification RFC 1006).

  • The line number is not used, set on 1.

When the communication line is set as TCP Redundant you can configure an IP address and port of a backup device. If a communication process lost the connection or is unable to connect to the device, it will switch periodically between the configured devices. KOM process tries to connect to a primary device at first.
Note: Multiple IP addresses of primary/backup device can also be configured (separated by commas or semicolons).

Line protocol parameters


A dialog window of communication line configuration - Protocol parameters tab.
They influence some optional protocol parameters.

The following line protocol parameters are defined:

Parameter

Meaning

Unit / size

Default value

Parameter

Meaning

Unit / size

Default value

Rack

Siemens Simatic rack number. Rack 0 is most often used.

0 to 7

0

Slot

Siemens Simatic slot number. Slot 2 is most often used.

0 to 31

0

S7 Subnet ID-part 1 (hex)

S7 subnet address sent as a part of Remote TSAP if parameter Use long TSAP is set to True

0x0 to 0xFFFF

0

S7 Subnet ID-part 2 (hex)

S7 subnet address sent as a part of Remote TSAP if parameter Use long TSAP is set to True

0x0 to 0xFFFF

0

 Use Secondary

The parameter allows the use of redundant PLCs, which may differ in the settings of some parameters (Rack, Slot, S7 Subnet ID).

If its value is True, the primary and secondary parameters are used alternately when connecting to the PLC using the specified IP addresses.

-

False

Connection Resource (hex)

Connection resource, it enters as MSB byte to the calculation of the value of Remote TSAP at initialization of ISO Connection-request.
See the description of parameter Use long TSAP.
Note: in the specific case, when two systems (one of them D2000) needed to communicate with S7-300, they each had to have a different Connection resource, otherwise after sending the initial sequence of D2000 KOM process, the connection broke:

/TSK1/Sending CR-TPDU: CLASS=0, SRC-REF=0x0001, TPDU size=1024, SRC-TSAP=10-00, DST-TSAP=03-02
/TSK1/OUT-<03><00><00><16><11><E0><00><00><00><01><00><C0><01><0A><C1><02><10><00><C2><02><03><02>
recv error '10.94.11.237:102 (handle: 2888, objId: 2563271)' - WSA_ECONNRESET [ 10054] Task: L.N337-S7ExecTsk/TSK1/

After changing the Connection resource from 3 to 2, the communication started working.

0x0 to 0xFF

3

Local TSAP (hex)

ISO Local TSAP (Transport Service Local Point).  Source TSAP value during the initialization of ISO Connection-request.
See the description of parameter Use long TSAP.

0x0 to 0xFFFF

0x1000

Source Reference

ISO Source Reference. Value of SRC-REF during the initialization of ISO Connection-request.

0 to 65535

1

Use long TSAP

Enables a long format of local and remote TSAP which is sent during the connection setup phase.
Short TSAP is 2 bytes long.
Short local TSAP has the following format:

Short remote TSAP has the following format:

Long local TSAP is 28 bytes long. Last 2 bytes are higher and lower byte of parameter Local TSAP
Full remote TSAP is 28 bytes long and it contains:

-

False

MPI/Profibus Address

MPI/Profibus address sent as a part of Remote TSAP, if parameter Use long TSAP is set to True

0 to 126

1

ISO TPDU Size Variable Parameter

The maximum required size of ISO TPDU. The parameter value the initialization of ISO Connection-request.

8192, 4096, 2048, 1024, 512, 256 or 128 bytes

1024 bytes

Nr. of Parallel Network Threads

Maximum parallel communication threads. Increase the value if there is a request on more data read from the device in a shorter time.

1 to 4

1

Cycle Time

The required time of one data reading cycle.

ms

1000 ms

Message Timeout

Maximal wait time on a reply from the device.

ms

2500 ms

Inter Message Delay

Delay which is used before sending a data request. When a high data transfer rate is required, set 0 ms.

sec.ms

20 ms

Reconnect Delay

Delay before reconnection to the device if the connection has failed or some communication error has occurred.

sec.ms

2 sec

Connection Error Timeout

When Timeout passes and communication error occurs in all threads, a communication error status is set on the stations. FALSE state is set on the communication line.

sec.ms

20 sec

S7 PDU Size

Maximum PDU in bytes at S7 communication with the device.

240, 480, 960 bytes

480 bytes

Tcp No Delay

Setting Tcp No Delay parameter causes low-level socket option TCP_NODELAY to be set, thus turning off the default packet coalesce feature.

-

False

Debug Values

Activates a debug info about the loaded values of I/O tags. Use this parameter only when communication must be debugged because it highly uses CPU and slows down the communication.

YES/NO

NO

Debug I/O Binary Packets Info

Activates a debug info about a binary content of packets. Use this parameter only when communication must be debugged because it highly uses CPU and slows down the communication.

YES/NO

NO

Debug Requests Info

Activates a basic debug info about requested data.

YES/NO

YES

Debug Answers Info

Activates a basic debug info about received packets.

YES/NO

YES