MICROTEL 700
MICROTEL 700 communication protocol
Supported device types and versions
Communication line configuration
Communication station configuration
Alternative communication path
I/O tag configuration
Redundant system
Errors and problems
Detail implementation of protocol
Tell commands
Literature
Changes and modifications
Document revisions
Supported device types and versions
-
Communication line configuration
Category of communication line: Serial, SerialOverUDP Device Redundant, RFC2217 Client, TCP/IP-UDP
Parameters of serial line according to the setting of telemetry system.
UDP Parameters:
The parameters of primary server or secondary (or parameters of primary/secondary network interface in case of a server with multiple network interfaces) one are mandatory.
Host: string max. 80 characters – a server name in the INET form (the name or numerical address a.b.c.d).
Port: UDP port number (1 to 65535).
Global parameters:
Key word | Full name | Description | Unit / size | Default value |
|---|---|---|---|---|
SCAN | Scan | Permanent passive mode (Scan only) only for data reading (mode 2). | YES/NO | NO |
MOXAT | Moxa Timeout | Setting of timeout for change to other communication device on SerialOverUDP Device Redundant line. If the valid data are not received from communication device till timeout, the other device is used (backup or primary, if it is configured). | 20 | sec |
Communication station configuration
Communication protocol: Microtel 700.
Station address is a number within the range 1 to 253. Do not use the addresses 0, 254 and 255. They are filtered because they often occur at the beginning of response (error in transmission system).
Parameters of station protocol
Dialog window of station configuration - tab "Protocol parameters".
Table 1
Key word | Full name | Description | Unit / size | Default value |
|---|---|---|---|---|
RC | Retry Count | Number of retry calls when error in communication occurs. | - | 2 |
RT | Retry Timeout | Delay between retry call if a communication error occurs. | ms | 500 millisec. |
WFT | Wait First Timeout | The first waiting for a response after sending a call. | ms | 300 millisec. |
WT | Wait Timeout | Delay between the readings of a response until it is completed. | ms | 200 millisec. |
MWR | Max Wait Retry | Number of retry response reading until it is completed. | - | 20 |
MODULE_CNT | Module Count | Maximum number of modules that are required in one call. The value must be in the range of 1 to 5. If not, the default value is used. | - | 5 |
INV_MOD | Inversed Modules | An analyze of sectors that have been changed (the function COS - CHANGE OF STATE) is done in inverse order: bit 0 LSB - modules 0..7, | YES/NO | NO |
AHOST | Alternative Path Host(s) 1, 2 | The configuration of so-called alternative communication path. |
|
|
APORT | Alternative Path Port 1,2 | UDP ports to which data will be sent when using the alternative communication path. |
| 0 |
APRC | Alternative Path Retry Count | Number of retry call if the alternative communication path is used. | - | 2 |
APUT | Alternative Path Use Timeout | After the elapse of the defined time since the start of using alternative communication path, the viability of communication through standard path is tested again according to the communication line configuration. | sec | 600 |