MODBUS SCT PPU

MODBUS SCT PPU

MODBUS SCT PPU communication protocol

Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions

Supported device types and versions


This protocol supports the communication with the telemetric stations for remote measurement on gas meters of SCT company. It ensures the parallel measurement of data from the meters for wholesale gas consumption and medium one of SPP-Distribúcia a.s. .

Communication line configuration


Communication station configuration


  • Communication protocol "MODBUS SCT PPU".

  • Station address is a decimal number in the range of 0 to 255 (usually 1).


Station protocol parameters

Communication station - configuration dialog box - tab Protocol parameters.
These parameters influence some of optional protocol parameters. You can define the following station parameters:

Table 1

Parameter

Meaning

Units

Default value

Retry Count

Maximum retries of call. If any response is not received after these callings, the station switches to the communication error state.

-

2

Retry Timeout

Timeout before the retrying the call if any response has not been received.

ms

500

Wait First Timeout

Timeout between sending the call and first reading the response.

ms

200

Wait Timeout

Timeout between the response readings.

ms

200

Max. Wait Retry

Maximum retries of reading the response.

-

30

Send Valid Data Only

Send only valid data to D2000 System kernel. If it is set on YES, the Invalid values are not send to the system.

YES/NO

YES

Future Data Filter

Filtering data that has a time stamp shifted forward by this value from the current time (in hours). The setting on 0 hours switches off this filter.

0-168 hours

24

History Data Filter

Filtering data that have the time stamp shifted back by this parameter from the current time (in days). The setting on 0 days switches off this filter.

0-730 days

31

Full debug

Extra debug information about communication on the line including debug information about all gained I/O tag values.

YES/NO

NO

I/O tag configuration


I/O tags for non-variable mode: Ai,Ci,TiA


I/o tag address:

Table 2 contains the list of supported I/O tag addresses. The address is in the text format - the value from the column "Address".

Table 2

Address

Value type

Tech. units

Meaning

VER

Ci

-

Protocol version (0x01).

ECSID

Ci

-

ID of conversion device, it is numbered from 0.

RTURDTM

TiA

-

RTU  time of last reading the current data from the conversion devices.

ECSDTM

TiA

-

Time on the conversion device when the last reading the current data.

P

Ai

kPa

Current absolute pressure.

T

Ai

°C

Current temperature.

F

Ai

m3/hour

Instantaneous flow.

CLO

Ai

m3

Current status of counter for calculated quantity of LO.

CHI

Ai

m3

Current status of counter for calculated quantity of HI.

C

Ai

m3

Current status of counter for calculated quantity, calculated as C = 10000 * CHI + CLO.

C8LO

Ai

m3

Status of counter for calculated quantity at 8:00 - LO.

C8HI

Ai

m3

Status of counter for calculated quantity at 8:00 - HI.

C8

Ai

m3

Status of counter for calculated quantity at 8:00, calculated as C8 = 10000 * C8HI + C8LO.

VH

Ai

m3

Calculated quantity for the previous hour.

VD

Ai

m3

Calculated quantity for the previous day.