Jablotron 100
Supported device types and versions
The Jablotron 100 protocol enables communication with the RS-485 - JA-121T bus interface of the JABLOTRON 100 Alarm system.
The Jablotron 100 protocol is implemented as an ESL script using the Generic User Protocol.
Serial interface parameters:
RS485 (two-wire connection)
9600 baud
8 data bits
no parity
1 stop bit
The protocol supports:
determining the state of the section/sections 1-15: the STATE command
checking the status of PG outputs 1-128: the PGSTATE command
determining the status of peripherals 0-229 (really only 0-30 were present): the PRFSTATE command
enabling/disabling protection in sections: SET, SETP, UNSET commands
switching on/off PG outputs: PGON/PGOFF commands
Both the active mode of communication (interface spontaneously sends changes) and passive mode (periodic polling is required) are supported.
The received values are stored in D2000 in structured variables (sections/peripherals/PG outputs).
Literature
Document revisions
Ver. 1.0 - March 21st, 2024 - Document creation.