Fisher-Rosemount RS3 SCI
Fisher-Rosemount RS3 SCI communication protocol
Supported device types and versions
The protocol supports data transmission from/to the SCI (Supervisory Computer Interface) interface of the Fisher-Rosemount RS3 control system.
Communication line configuration
communication line category: Serial, SerialOverUDP Device Redundant.
Transmission parameters either 19200 or 38400 Baud (see the tab. nr. 1), 8 data bits, 1 stop bit, no parity.
For the correct communication of a Rosemount RS3 SCI device, these SCI parameters must be set:
Table 1
Parameter | Value |
|---|---|
Comm Port Baud Rate | 9.2 kbs or 38.4 kbs |
Checksum | Yes |
Data Bits and Parity | 8N |
XON/XOFF Control | Off |
EIA Option | None |
Reply Header String in Hex format | 00 00 00 00 |
Reply Trailer String in Hex format | 00 00 00 00 |
Mode | Async Length LSB |
Data Format | IEEE |
TX Gap | 100 ms |
Communication station configuration
Communication protocol: Fisher-Rosemount RS3 SCI.
Address parameters require to specify the First index and Update Interval parameters.
First index: A value within the interval 0..1499, address of the first I/O tag in the SCI table (Table Entry Location Number).
Update interval: Time period for the acquisition of new I/O tag values. Possible settings: cont. (continuously), 5 sec., 10 sec., 15 sec., 30 sec., 1 min., 2 min., 5 min., 15 min. and 60 min.
SCI allows configuring acquisition of 1500 system values into its table (Table entry) with different parameters (Scaling, Update interval). Table entries are allocated to individual I/O tags starting with the First index value. The station represents a logical set of tags with the same Update Interval parameter. Update Interval is a time period with which the SCI acquires new values from the Rosemount S3 system.
Note: As the SCI configuration allows to define the parameter Update Interval up to 300 seconds (5 min.), this setting is used for station polling periods of 15 and 60 minutes.
Station protocol parameters
The following station protocol parameters can be defined:
Table 2
Keyword | Full name | Meaning | Unit | Default value |
|---|---|---|---|---|
RC | Retry Count | Request repetition count in case of a communication error. | - | 2 |
RT | Retry Timeout | The delay between request repetitions in case of a communication error. | ms | 200 |
WFT | Wait First Timeout | The delay after transmitting the request and before reading the response. | ms | 60 |
WT | Wait Timeout | Delay between response readings until its finalization. | ms | 200 |
MWR | Max Wait Retry | Repetition count of response readings until its finalization. | - | 15 |
DEBUG | Debug Mode | If the value of the parameter is YES, the tables on the side of the SCI device are not configured during communication (deletion from tables + initialization of individual points). | YES/NO | NO |
SW | Send Weak | If the value is YES - if a new I/O tag value with an error attribute is acquired, the error number will be sent to the I/O tag value and the value is marked by the WEAK attribute. It is used for debugging purposes only. | YES/NO | NO |
A string containing the protocol parameters is being defined as follows: