Remia E3

Remia E3

Remia E3 communication protocol

Supported device types and versions


This protocol supports data reading/writing from a controller of quarter-hour maximum Remia EEE.

Communication line configuration


  • Communication line category: Serial, SerialOverUDP Device Redundant, TCP/IP-UDP.

  • Parameters of the serial line:

    • Baud rate - 1200 Baud

    • No parity, 8 data bits, 1 stop bit

  • Parameters of UDP line:

    • Host: IP address of the controller

    • Port: UDP port of the controller where requests are sent.

    Note: The parameters of the backup server (Host and Port) are not used in this protocol.

Communication station configuration


  • Communication protocol: Remia E3.

  • The station address is set according to the address on a device (0 to 15) specified as a decimal number or as a hexadecimal number with a hash at the beginning (e.g. #6A).

Station protocol parameters

The configuration dialog box of station - the tab "Protocol parameters".

Table 1

Keyword

Full name

Meaning

Unit

Default value

RC

Retry Count

Maximum count of request retries. If no response returns after a request had been sent, the station's status will change to a communication error.

-

2

RT

Retry Timeout

Timeout before resending a request if no response has been received.

ms

100 ms

WFT

Wait First Timeout

The delay after sending the request and before reading the response.

ms

100 ms

WT

Wait Timeout

The delay between the response readings.

ms

300 ms

MWR

Max Wait Retry

The maximum number of retries of the response reading.

-

10

I/O tag configuration


I/O tag types: Ai, Ci, Co, Di, TiA, TiR.

The address is a number in the range from 0 to 300 (as a decimal number or as a hexadecimal number with a hash at the beginning, e.g. #0A).
The meaning of the addresses is stated in Table 2:

Table 2

Value type

Address

Description

Read/Write

Ai

Ai

0

Instantaneous power.

R

Ai

1

Average power.

R

Ai

2

Peak VT.

R

Ai

3

Peak NT.

R

Ai

4

Measurement 1 (main) - the last 1/4 hour (see Note).

R

Ai

5

Measurement 2 (secondary) - the last 1/4 hour (see Note).

R

Ci

Ci

0

The number of electrometers.

R

Ci

1

The number of regulatory degrees.

R

Ci

2

The number of appliances.

R

Ci

3

Regulatory degree.

R

Ci

4

Tariff (0=VT, 1=NT).

R

Ci

5

Current regulatory degree.

R

Ci

6

Current average power (%).

R

Co

Co

0

Regulated power VT.

R/W

Co

1

Regulated power NT.

R/W

Di

Di

0 až 7

Type of electro meter (FALSE=active power [kW], TRUE=reactive power [kVAr]).

R

Di

100 až 164

Appliances (FALSE=idle state, TRUE=control state).

R

Di

200 až 264

Status signal (FALSE=inactive, TRUE=active).

R

TiR

TiR

0

The time within a 15-minute interval.

R

TiA

TiA

0

Date and time of initialization.

R

TiA

1

Date and time of power failure.

R

TiA

2

Date and time of the configuration change.

R

TiA

3

Date and time of the last reset.

R

TiA

4

Current date and time.

R

TiA

5

Time to reach peak VT.

R

TiA

6

Time to reach peak NT.

R

TiA

7

Time of the last quarter-hour.

R