MODBUS Server
MODBUS Server communication protocol
Supported device types and versions
The protocol implements a server (slave) communication with arbitrary devices that support the MODBUS RTU standard, either in a serial communication version or a MODBUS over TCP/IP variant.
Communication line configuration
Line category: Serial (serial communication), SerialOverUDP Device Redundant (serial communication).
Line category TCP/IP-TCP (MODBUS over TCP/IP). Use a symbolic address ALL or *, in order for the KOM process to listen on a selected TCP port on all existing network interfaces. TCP port 502 is commonly used, but any of the ports can be used.
Line number - set the value, for example, 1.
Note: The KOM process works as a multitasking TCP server, and that is why it is able to handle multiple clients at the same time.
Line protocol parameters
Configuration dialog box - table Parameters.
They influence some optional parameters of the protocol. The following line protocol parameters can be set:
Table 1
Parameter | Meaning | Unit | Default value |
|---|---|---|---|
Silent Interval | A delay before the start of transmission of each data packet. | ms | 50 |
No Request Timeout | If the timeout passes and no valid request comes, all stations on the line will go to a communication error. However, the values of output I/O tags will not be invalidated (as this is a server protocol). | mi:ss | 1:00 |
Single Server | If the value of the parameter is set to YES, the KOM process replies with a SLAVE_DEVICE_FAILURE error to each request that is sent to a non-existent station (a station with an unknown address). If the value is NO, the KOM process ignores this request and does not send a reply to it. | YES/NO | YES |
Moxa Timeout | The switching time of Moxa redundant devices in case of a communication error or some problems. As this is a server protocol that waits for requests from external devices, a failure to receive a communication request for a longer time than the value of this parameter is considered to be an error. It is effective only for the SerialOverUDP Device Redundant line. | sec | 10 sec |
TCP No Delay | Setting the TCP No Delay parameter to YES causes the low-level socket option TCP_NODELAY to be set, thus turning off the default packet coalesce feature. | YES/NO | NO |
Redundancy Mode | The parameter specifies the protocol behavior in redundancy for the TCP/IP-TCP line category if the KOM process is not active:
| Passive NoBind | Passive NoBind |
Communication station configuration
Communication protocol "Modbus Server".
The station address is a decimal figure in the range of 1 to 247. Address 0 is reserved for broadcast.
It is possible to configure more stations with different addresses on one line; the KOM process will reply on behalf of every configured station. See also the line protocol parameters Single Server.
Station protocol parameters
Configuration dialog box - tab Parameter.
They influence some optional parameters of the protocol. Following station protocol parameters can be set:
Table 2
Parameter | Meaning | Unit | Default value |
|---|---|---|---|
Addressing model | Sets an address model of the MODBUS protocol: | MODBUS PDU | MODBUS PDU |
I/O tag configuration
Possible value types: Ai, Ao, Di, Do, Ci, Co.