ZPA INMAT 64/65

ZPA INMAT 64/65

ZPA INMAT 64/65 communication protocol

Supported device types and versions


This protocol supports data reading from the INMAT 64 and INMAT 65 dataloggers produced by ZPA Nová Paka (Czech republic).

Communication line configuration


Note:
A device sends data spontaneously (without the request for data). A delay between the transmitted data blocks is 5 seconds.

Communication station configuration


  • Communication protocol: ZPA INMAT 64/65.

  • The station address is not used. On one serial line, only one INMAT 64 or 65 can be connected.

Station protocol parameters

They are not used.

I/O tag configuration


I/O tags: Ai

The address can be entered as a decimal number or a hexadecimal number with a hash at the beginning (e.g. #A).

The value meaning:

Address

Cycle

Meaning

Units

0

1

Heat output

GJ/hour

1

1

1/4 hourly maximum

GJ

2

1

Heat output sum

GJ

3

1

Instantaneous mass flow rate

t/hour

4

1

Mass flow rate sum

t

5

1

Temperature

°C

6

1

Temperature difference [°C] - INMAT 64 or Operating pressure [MPa] - INMAT 65

-

7

2

Heat output

GJ/hour

8

2

1/4 hourly maximum

GJ

9

2

Heat output sum

GJ

10

2

Instantaneous mass flow rate

t/hour

11

2

Mass flow rate sum

t

12

2

Temperature

°C

13

2

Temperature difference [°C] - INMAT 64 or Operating pressure [MPa] - INMAT 65

-

Literature


-

Changes and modifications


-

Document revisions


  • Ver. 1.0 – February 23, 2001 – Creation of document