Hivus communication protocol
The Hivus communication protocol supports communication with control units (RJ) and dataloggers (HDL) produced by Hivus. The communication was implemented and tested with the RJ-05e control unit. The control unit is used to time control of performance and regulation of desoster devices (air ozonizers).
Category of communication line: Serial, MOXA IP Serial Library
Parameters of the serial line:
Baud rate: 19200 Baud
Parity: optional
Note: Parity MARK (sending the device address) and SPACE (all others) are set during transmission, so the parity setting is not important.Handshaking: none
Note: communication on the Serial line was tested on computer serial port, virtual serial port corresponding to MOXA NPort device, and virtual serial port corresponding to Serial/USB converter USB-COM GemBird.
Communication on MOXA IP Serial Library line was tested through the use of MOXA NPort 5450I.
Communication protocol: Hivus Controller
Station address: 1 Byte.
Address 0 is "broadcast" (each device responses to it, but only on reading by 02h function). I/O tag - type 105 (logger number) is used to detect the real address of the device.
Addresses 1-255 represents the common addresses of devices (04h function is used to read data).Time parameters - recommended polling period is 1 min (to avoid overloading the processor of the control unit by very frequent communication).
Station protocol parameters
Configuration dialog window - Communication station - field "Protocol parameters".
These parameters influence some optional parameters of the protocol. The following parameters can be used:
Tab. č. 1
Keyword | Full name | Description | Unit | Default value |
|---|---|---|---|---|
DBGI | Debug Input | Value 1 activates the listing of information about received values of I/O tags in the trace file of the line in the format: | - | 2 |
DBGO | Debug Output | Value 1 activates the listing of information about written values of I/O tags in the trace file of the line in the format: | - | 2 |
RAW | Read After Write | If the parameter is True, the writing of value (by 05h function) is followed by reading. | - | False |
Possible value types of I/O tag: Ai, Ao, Ci, Di, TxtO, TxtI.
I/O tag address is written in the format:
T=type - I/O tags without index
T=type;I=index - I/O tags with index (channels and signalization of failures on desoster)
T=type;I=index;J=index; - I/O tag contains raw data of protocol with address 100
The header, which is read from the control unit by the KOM process, contains the information that is mapped into I/O tags without an index (e.g. moto hours worked, number of engaged channels, type of control unit), information about channels and signalization of failures on desosters.
There can be configured 0 up to 8 channels. Each channel is defined by characteristics (1-15, see table below), value, upper/lower limit (something like upper/lower limit in D2000). The channels can be addressed in two ways:
consecutive number 1-8:
order within channels with particular characteristics. Instantaneous value of i-th measurements with characteristic t is addressed by T=t, I=i.
For example, instantaneous value of third measurement of type 1 [temperature] is defined by T=1, I=3 no matter on which channel this temperature occurs.
Signalization of failures on desoster enables to read the statuses of desoster 1..10 that are connected to concentrator 1 (T=101) or concentrator 2 (T=102).
These I/O tags can be configured:
Table 1 - I/O tags for channels
Address | Value type | Meaning | ||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
T=type;I=index | Ai, Ci, Di | Reading of instantaneous value of measurement of typ type, which is index-th in order.
| ||||||||||||||||||||||||||||||||
T=16;I=index | Ai, Ci, Di | Reading of instantaneous value of channel with index. The index can be from range 1..8. | ||||||||||||||||||||||||||||||||
T=17;I=index | Ai, Ci | Reading of channel characteristics with index. The index can be from range 1..8. | ||||||||||||||||||||||||||||||||
T=18;I=index | Ai, Ci | Reading of upper limit of the channel with index. The index can be from interval 1..8. | ||||||||||||||||||||||||||||||||
T=19;I=index | Ai, Ci | Reading of lower limit of the channel with index. The index can be from interval 1..8. |
Table 2 - I/O tags - raw data from the protocol
Address | Value type | Meaning |
|---|---|---|
T=100;I=index;J=index | TxtI | Reading the raw data from the protocol header into the text I/O tag. "I" and "J" indicates the beginning and end byte (1-128), and this condition must be valid: I<=J. |
Table 3 - I/O tags relating to fault conditions of desoster
Address | Value type | Meaning |
|---|---|---|
T=101;I=index | Ai, Ci, Di | Reading of signalization of device failure with an index that is connected to concentrator No. 1 (if T=101) or concentrator No. 2 (if T=102). |
Table 4 - I/O tags without indexes
Address | Value type | Meaning |
|---|---|---|
T=103 | Ai, Ci | Worked moto hours - value from range 0-999 999. |
T=104 | Ai, Ci | The number of connected sensors - value from range 0-8. The channels with connected scanners have valid values (I/O tags of types 1 to 19 - see table 1), other channels have invalid values. |
T=105 | Ai, Ci | The control unit number (equal to the station address). It is used to detect the real address of the station if the station address will be 0 (broadcast). |
T=106 | TxtI | 3-sign string that defines the type of device:
|
T=107 | Ai, Ao | Setpoint for controlling ozone (O3) in ppm. Also, the writing of value is supported (the protocol function 05h). |
T=108 | Ai, Ao | The threshold for an indication of the O3 level in ppm. Also, the writing of value is supported (the protocol function 05h). |
T=109 | TxtI, TxtO | 16-sign string - upper and lower limits for the printer. Also, the writing of value is supported (the protocol function 05h). |
T=110 | TxtI, TxtO | 16-sign string - comment of print. Also, the writing of value is supported (the protocol function 05h). |
T=121 | TxtO | Writes values to control unit (by protocol function 01h). Supported values:
|
T=122 | TxtI, TxtO | Writes 32-bytes of limit values into the control unit (by the protocol function 05h). |
-
-
Ver. 1.0 - April 23, 2015 - creating the document
Related pages:
Although this protocol was implemented, it is not currently part of the D2000 KOM. In case of interest, please contact the D2000 development department.