Advantech ADAM 4000

Advantech ADAM 4000

Advantech ADAM 4000 Series communication protocol

Supported device types and versions
Communication line configuration
Communication station configuration
I/O tag configuration
Literature
Changes and modifications
Document revisions

Supported device types and versions


The protocol allows reading and writing data into the Advantech ADAM series 4000 devices.

Types of usable I/O tags according to ADAM type are listed in the following table:

Table 1

Type and range of measurements

ADAM device type

Read/Write

1 x analog input AI

4011, 4011D, 4012, 4013, 4014D, 4016

R

8 x analog input AI

4017, 4018, 4018M, 4019

R

1 x analog output AO

4021

R/W

4 x analog output AO

4024

R/W

4 x digital output DOUT

4060

R/W

8 x digital output DOUT

4068, 4069

R/W

12 x digital output DOUT

4056S, 4056SO

R/W

8 x digital input DI

4052, 4068

R

16 x digital input DI

4051, 4053

R

Communication line configuration


Required line parameters:

Communication station configuration


  • Communication protocol: Advantech ADAM Series 4000

  • Station address – Module Address - ADAM module address (according to the setting of modules in configuration), a number in the range of 0 to 255 specified either as a decimal number or a hexadecimal number with a hash at the beginning (e.g. #1A).

  • Time parameters – polling parameters – for optimal and quick communication - Delay 0 seconds (all stations).

 

Station protocol parameters

Configuration dialog box - tab „Parameters".
They influence some optional parameters of the protocol.

Table 2

Full name

Meaning

Unit

Default value

Retry Count

A retry count of the request in case of a communication failure.

-

2

Retry Timeout

The delay between request retry in case of a communication failure.

ms

300 milliseconds

Wait First Timeout

The delay after sending the request before reading the response.

ms

200 milliseconds

Wait Timeout

The delay between response readings till its completing.

ms

200 milliseconds

Max Wait Retry

Retry count of response reading till its completing.

-

8

Checksum

Using the checksum. Set according to the setting of module ADAM in the configuration.

YES/NO

YES

For further information on protocol parameters, see the topic Communication line - configuration dialog box.

I/O tag configuration


I/O tag address requires two parameters: