Telegyr 809 Server communication protocol
This protocol implements the server-side of Telegyr TG809 standard. There is supported a configuration in both line and system redundant configurations.
Communication line category:
TCP/IP-TCP
Note: As TG809 Server is a server protocol, the KOM process works in a TCP server mode, i.e. it listens on an IP address and port specified in the configuration of TCP/IP-TCP communication line.
It is possible to use a symbolic address ALL or * - in this case, the KOM process listens on a chosen TCP port in all network interfaces which are available.
Communication protocol: Telegyr 809 Server
Address of station: integral number from the interval 0-1023. In the protocol, the address of the station is used as a station's number (Stationsnummer).
Configuration dialog window - tab "Protocol parameters".
They influence some optional parameters of the protocol.
Table 1
Parameter | Meaning | Unit | Default value |
|---|---|---|---|
Communication Line | A number from range 0-255 defining the "Communication number" parameter in the protocol telegrams. | - | 0 |
Line Alive Timeout | Timeout for detection of failure of the master side of communication. | sec | 7 |
Read Wait Timeout | The delay between reading data from the communication line. | ss.mss | 00.050 |
MOXA Timeout | Timeout for detection of failure of one communication line on the redundant lines. After elapsing the timeout since receiving the last character, the communication is redirected to another communication line, i.e. reading/writing will be done via secondary/backup device. | mi:ss | 00:10 |
Max Data Size | The maximum number of data bytes in a single packet. This parameter defines the approximate value (can be exceeded by a data size of one output I/O tag). The standard defines maximum data size equal to 255 bytes but decreasing the packet size practically solved a particular packet fragmentation problem in WAN communication. | - | 210 |
System Redundancy: Manages A Status Address | HW address of output I/O tag with the status of system redundancy. The format of the HW address is Rack.Chassis.Slot.Point or Rack-Chassis-Slot-Point, for example, "0-2-15-1". | - |
|
Is Substation | On every line, there should be only one station (called the main station) that has this parameter set to False. All other stations (called substations) should have this parameter set to True. This emulates the situation when there may be several substations behind the main station. Requests from the master which do not contain the station number, are related to the main station. | - | False |
Scan-only Mode | In scan-only mode, data is being read and analyzed, but no data is sent. Combined with the parameter Full Debug this parameter enables the KOM process to be used as an analyzer of TG809 communication. | - | False |
No Point No Answer | If the I/O tag with an address that is in the request from the TG809 server is not found, the KOM process will not send any response. | - | False |
Full Debug | Enables detailed listings about sending and receiving values. | - | False |
Possible I/O tags: Ai,Ao,Di,Dout,QI,Ci,Co
Address of I/O tags: either software or hardware address
software address - a number from interval 0 - 32767
hardware address - consists of the following components:
Rack - a number from interval 0 - 3
Chassis - a number from interval 0 - 5
Slot - a number from interval 0 - 15
Point - a number from interval 0 - 31
For I/O tags of Ai and Ci type, you must define the minimum and maximum range - Min and Max. The values will be calculated for this range (from range -32000 … 32000 supported by protocol).
For I/O tags of Ao and Co, you must define the minimum and maximum range - Min and Max. Same as for input I/O tags but in addition the values out of defined range will be sent as the values -32000 or 32000.
I/O tags of Dout type have supplementary options:
"Four-criterion indication". If it is active, the VKM bit is set when sending the value. This bit indicates that the value is 4-state (Quadrat). This status allows, in addition to False (binary 01) and True (binary 10) to transmit also Invalid (binary 00 or 11).
"Indication with time tag". If it is active, IAC 2 message (Indication with time tag) containing the time stamp (hour/min/sec/ms) will be used to send the value. If it is inactive, IAC 1 message (Indication without time tag) is used.
-
-
Ver. 1.0 – July 16, 2015 – created document
Ver. 1.1 – July 11, 2017 – Support of IAC 2 (message with a timestamp)