VONSCH VQfrem 400

VONSCH VQfrem 400

VONSCH VQfrem 400 protocol

Supported device types and versions


The protocol is used for communication with vector control frequency converters VQfrem 400 (for 3 x 400 V motors) from VONSCH. Reading values from inverters is supported. Commanding or writing values is not supported.

Communication line configuration


  • Communication line category: Serial, SerialOverUDP Device Redundant (serial communication).

  • Note: serial communication has been tested with a VQfrem 400 with 609h firmware.
    Serial line setting: 19200 baud, 8 bits, no parity, 1 stop bit, RS-485 interface.
    The serial line speed is configurable on the drive (2400 - 19200 baud).

Communication station configuration


  • Communication protocol: VONSCH VQfrem 400.

  • The station address is a 16-bit number (1-32767). It can be entered decimally (e.g. 1 or 1234) or hexadecimally using a hash (e.g. #0001 or #4D2).
    Address 32768 (#8000) serves as a broadcast for commanding - all devices receive it, but none respond to it.

Station protocol parameters


Communication station - configuration dialog box - tab Protocol parameters.
They influence some of the optional parameters. You can set the following station protocol parameters:

Table 1

Parameter

Meaning

Unit

Default value

Full Debug

Logging of detailed debug information about communication in the line log.

-

NO

Retry Count

Maximum count of request retries. If no response returns after a request had been sent, the station's status will change to a communication error.

-

2

Retry Timeout

Timeout before resending a request if no response has been received.

ss.ms

0.1

Wait First Timeout

The delay after sending the request and before reading the response.

ss.ms

0.1

Wait Timeout

The delay between the response readings.

ss.ms

0.1

Max Wait Retry

The maximum number of retries of the response reading.

-

6

I/O tag configuration


I/O tags: Ai, Ci

I/O tag address

The address of the I/O tag is a 16-bit number (1-65535). It can be entered decimally (e.g. 1 or 1234) or hexadecimally using a hash (e.g. #0001 or #4D2).

Table 2 - quantities available for reading according to the documentation

Address

Description

Meaning

Address

Description

Meaning

#0001

Software version

609h for ver. 6.09, (402h for ver. 4.02, 304h for ver. 3.04)

#0004

Voltage range

190h for 400V, 191h for 400 ...M, 2b2h for 690V

#0025

Freq. INV - the frequency of voltage on converter’s output (stator frequency) 

+/- XXX,XX Hz

#0026

Revolves - output revolutions of the motor

+/- XXXX rev/min

#0027

Revol/i - evolutions behind gear/transmission

+/- XXXX,X rev/min

#0028

Freq.RT - rotor frequency (evaluated from speed encoder – IRC)

+/- XX,XX Hz

#0029

Freq.RF - required converter frequency

+/- XX,XX Hz

#002A

MT Curr. - effective current value into the motor

XXX,X A

#002B

R.torque - required mechanical motor torque 

+/- XXX,X Nm

#002C

Torque - mechanical motor torque 

+/- XXX,X Nm

#002D

Mag. flux - rotor magnetic flux

X,XXX Wb

#002E

Volt. MT - momentary motor supply voltage (100.0% responds to 400 V)

XXX,X %

#002F

Volt. DC - real voltage of converter’s unidirectional DC bus

XXX V

#0030

Inp.pow. - momentary input power into the motor

XXX,X kW

#0031

MT power - motor power

XXX,X kW

#0032

kW hours - motor energy consumption in kWh

XXXX kWh

#0033

MW hours - motor energy consumption in MWh

XXXX MWh

#0034

Teplota chladiča meniča

XX,X °C

#0035

Temp.INV. - air temperature in the converter

XX,X °C

#0036

PR ref. - required value of process regulator

XX,X %

#0037

PR real - feedback of process regulator (real value)

XX,X %

#0038

Inp. AIN1 - the value of analogue input AIN1 in % range

XX,X %

#0039

Inp. AIN2 - the value of analogue input AIN2 in % range

XX,X %

#003A

Hodnota analógového vstupu 3 v % rozsahu

XX,X %

#003B

BIN 1-6 - status of binary inputs BIN 1 - BIN 6 (bits 0-5 from the received value - bit numbering is from 0 to 15). 

0=input is open
1=input is closed

#003C

RELAY 1-2,3 - the status of relay inputs RELAY 1 - RELAY 4  (bits 8-10 from the received value - bit numbering is from 0 to 15). 

0=relay is open
1=relay is closed

#003D

Hours INV - converter operating time counter

XXXX h

#003E

Hours MT - motor operating time counter

XXXX h

#003F

Pos.ref. - required position in a case of „position“ variable

+/- XXXX,X cm

#0040

Position - real position

+/- XXXX,X cm

#0041

Pos. TSW2 - the trajectory for running down when Terminal switch TSW2 is on

+/- XXXX cm

#0042

Deviation from zero position when calibrating the ARC position sensor

XXXX d

#0043

cos(fi ) - momentary value of motor power factor

+/- X,XX

#0044

See Warnings register 2

-

#0045

See Warnings register 1

-

#0046

See Faults register

-

#0048

Overload - a momentary value of overload

XXX.X %

#0049

Service SL - service displayed variable Slave

+/- XXXX d

#004a

Service MS - service displayed variable Master

+/- XXXX d