Historical Value Representation (Work with D2000 HI)

Historical Value Representation (Work with D2000 HI)

Historical value representation

Meaning of the buttons placed in the dialog box is following:

 

Button

Meaning

Export

Saves values displayed in the table into a file. Clicking the button opens the menu allowing to save values in a text file, CSV file or to copy them into the clipboard. It is also possible to save either all the values of the table (the All values item) or only selected values (lines).

Columns

Configuration of columns displayed in the table.

Edit

Edits selected value of the archive object.

Delete

Deletes selected value of the archive object.

Insert

Inserts a new value into the current table position.

Shows values of the archive object in graph.

Close

Closes the dialog box of the archive object.

 

Note: The buttons Edit, Delete, Insert are disabled if an archive object disallows this activity from HI.

 

The parameters Row and Column are enabled if the browsed archive object is a structure. When changing row (Row parameter) or column (Column parameter) of the particular archive object and clicking on button

, it loads data from archive. The change is indicated by red colour of the parameter Row or Column. You can see the current values in the object name in a title bar.

 

The button 

refreshes the displayed data of the archive object.

If the archive contains more values for given time interval than may be displayed in the dialog box, you must use the paging functions. For easy orientation and moving within the multi-page list you can use the buttons located below the list.

Paging buttons
Paging buttons

Table description

 

Besides particular values of an archive object, each table line contains other information concerning the given value. Their displaying depend on the table column settings. Table has the following structure:

 

Column

Contents

Time

Information about the time when the value was saved into the archive database. If the msec parameter is checked then the column displays time data with the millisecond accuracy. Checked Year parameter allows to display information about current year.

Value

Value of the archive object (object Historical value type) in corresponding time. If it contains “???” string, this value is not valid.

Limits

Limit state of the value: InLimit, VL-Limit,L-Limit, H-Limit, VH-Limit, LimitsProblem

Value state

Process state of the value: Invalid, ProcAlarm, NoAckPAlarm, PrAlSilent, Weak, NoAckValue, Transient, Default, Manual, PrAlCrit.

Archive flags

Flags: START, STOP, BLOCK, UNBLOCK, DELETED, USERMODIFY, OLDVAL, PROCESMODIFY, LOADDATA, MONO_TIME, K

Value flags

Flags of the value. This column displays only the flags with TRUE value.

 

Colors in table:

 

  • White color - data from the archive database. An editing is enabled.

  • Red color - data from the archive database. An editing is disabled.

  • Grey - life data from the graphs. An editing is disabled.

 

The descriptions of  individual value states are explained in the following table.

 

Value state

Meaning

INLIMIT

The value is at once greater than the low limit (Low Limit) and less than the high limit (High Limit).

VL_LIMIT

The value is less than the lowest limit (Very Low Limit).

L_LIMIT

The value is less than the low limit (Low Limit).

H_LIMIT

The value is less than the high limit (High Limit).

VH_LIMIT

The value is less than the highest limit (Very High Limit).

LIMITSPROBLEM

Condition VLL < LL < HL < VHL is violated.

TRANSIENT

The command to set value was issued at the moment of the value writing into the archive database, but backward reading has not verified the value setting.

DEFAULT

The value in Default mode (default value).

WEAK

Suspicious value (Weak Value). This value is not valid in the system because all the validity conditions are not met, yet.

INVALID

Invalid object value.

ProcAlarm

The state is occurred in case that the given object has an active process alarm.

NoAckPAlarm

The state is occurred in case that the process alarm is not acknowledged by operator in process D2000 HI.

PrAlSilent

The state is occurred in case that the given object hasn't any active process alarm, or Silent option is enabled at configuration of object process alarms in the process D2000 CNF.

NoAckValue

The state is occurred in case that the last object value change is not acknowledged by operator in process D2000 HI.

Manual

The object value is in Manual state, if it is manually adjusted by operator in process D2000 HI.

PrAlCrit

The status is occurred in case that the process alarm is defined as critical one in the process D2000 CNF.