Configuration of System Texts (Value Representation Methods)

Configuration of System Texts (Value Representation Methods)

Configuration of system texts

Configuration of system texts is performed by means of the process D2000 CNF.

Configuration of system texts
Configuration of system texts

The system texts are divided into the following categories:


The objects, values of which do not contain system texts:

  • I/O tags of AI, AO, CI, CO, TiA, ToA, TiR, ToR, TmRo, TxtI a TxtO types

  • Evaluated tags

  • User variables of Integer, Real, TmA, TmR, Txt types

* Displaying of values of Integer, Real, Absolute time and Time interval types might be controlled by transformation palette.


Boolean values

Label in the system

Predefined label

Cause

B_False

False

False value

B_True

True

True value

B_Oscillate

Oscilate

Oscillating value (TRUE <-> FALSE).



Di, Do measured values

Label in the system

Predefined label

Cause

D_False

OFF

False value

D_True

ON

True value

D_Oscillate

OSCILATE

Oscillating value (TRUE <-> FALSE). The system sets the value as the oscillating one according to defined parameters of filtering - Oscillation limits.



Process object values

Label in the system

Predefined label

Cause>

P_Run

Run

The process is running.

P_Crash

Crash

The process is terminated by an error (incorrect termination). If it is possible, D2000 Server will try to start the process again.

P_Stop

Stop

The process is correctly terminated.

P_WDErr

WDErr

Error when communicating with D2000 Server - Watch Dog Error (interrupted flow of Watch Dog messages between the client process and D2000 Server).



System alarm values

Label in the system

Predefined label

Cause

A_Norm

Normal

The condition to raise the alarm is not met.

A_Alarm

Alarm

The condition to raise the alarm is met.

A_Kvit

Kvit

The alarm is acknowledged by operator.

A_Block

Block

The alarm is blocked by operator, or at the alarm configuration is enabled Blocked alarm option.

A_UnBlock

UnBlock

The process D2000 Alarm is not running and operator unblocks the given alarm in Blocked state.

A_NoKvit

NoKvit

The condition to finish the acknowledge-required alarm is met before its acknowledgement.



Station values

Label in the system

Predefined label

Cause

St_On

ON

The station communicates

St_Off

OFF

The station does not communicate. The communication is disabled by operator (via the control window in process D2000 HI) or at the station configuration in the process D2000 CNF.

St_CommErr

COMERR

The occurrence of a "soft" error of the communication. Such error is occurred after an unsuccessful data transmission.

St_HardErr

HARDERR

The occurrence of "hard" error of the communication. Such error is occurred, if the communication with station is in StCOMERR state within the period given by Time filter parameter. If the station value is StHARDERR, then all the I/O tags of the station will pass to undefined state.

St_Simul

SIMUL

Communication with the station is simulated.

St_Wait

WAIT

The station is in AUTO mode. Communication is stopped. The control object value is TRUE. Requests for output are postponed and they will be executed when the control object value will be FALSE.



Qi measured values

Label in the system

Predefined label

Cause

SwTrans

TRANS

Change of quadrature value from TRUE into FALSE or vice-versa.

SwOff

OFF

False value

SwOn

ON

True value

SwErr

ERROR

Invalid (illegal) value.

SwOsc

OSCILATE

Oscillating value (TRUE <-> FALSE). The system sets a value as the oscillating one according to defined parameters of filtering - Oscillation limits.



Process alarms

Label in the system

Predefined label

Cause

NoAlarm

NoAlarm

No process alarm is active

ToTrue

ToOn

Process alarm occurred - change into ON (TRUE) level.

ToFalse

ToOff

Process alarm occurred - change into OFF (FALSE) level.

True

On

Process alarm occurred - ON (TRUE) level.

False

Off

Process alarm occurred - OFF (FALSE) level.

Invalid

Err

Invalid (illegal) value.

Oscillate

Oscillate

Oscillating value.

HL

HL

Process alarm occurred - limit state of HL value.

VHL

VHL

Process alarm occurred - limit state of VHL value.

LL

LL

Process alarm occurred - limit state of LL value.

VLL

VLL

Process alarm occurred limit state of VLL value.

ToHL

ToHL

Process alarm occurred- value change into HL limit state.

ToVHL

ToVHL

Process alarm occurred- value change into  VHL limit state.

ToLL

ToLL

Process alarm occurred - value change into LL limit state.

ToVLL

ToVLL

Process alarm occurred - value change into  VLL limit state.

SwToTrans

SwToTrans

Process alarm occurred - change of quadrat value into Q_Trans value.

SwToOff

SwToOff

Process alarm occurred- change of quadrat value into Q_Off (FALSE) value.

SwToOn

SwToOn

Process alarm occurred- change quadrat value into Q_On (TRUE) value.

SwToError

SwToErr

Process alarm occurred - change of quadrat value into Q_Err value.

SwTrans

SwTrans

Process alarm occurred- quadrat value is Q_Trans.

SwOff

SwOff

Process alarm occurred - quadrat value is Q_Off.

SwOn

SwOn

Process alarm occurred - quadrat value is Q_On.

SwError

SwErr

Process alarm occurred - quadrat value is Q_Err.

ErrorWriteCmd

ErrWriteCmd

Error at the setting of output tags.

Sw_ErrorCmdOn

ErrCmdOn

Error during cm_SetSwitchOn command execution.

Sw_ErrorCmdOff

ErrCmdOff

Error during cm_SetSwitchOff command execution.

Sw_ErrorBkpCmdOff

ErrZalCmdOff

Error during cm_SetSwitchBkpOff command execution.

Change

Change

Process alarm occurred - change of integer or analog value.

SysPrAl

SysProcAlarm

Special type of process alarm used just for two objects of System variable type - SystemError and SystemWarning.



Value limits

Label in the system

Predefined label

Cause

Is_InLimit

InLimit

The object value is at once greater or equal to LL and less or equal to HL (LL<=values<=HL).

Is_VL_Limit

VL_Limit

The object value is less than VLL (value<VLL).

Is_L_Limit

L_Limit

The object value is at once greater or equal to VLL and less than LL (VLL<=value<LL).

Is_H_Limit

H_Limit

The object value is at once greater than HL and less than VHL (HL<value<=VHL).

Is_VH_Limit

VH_Limit

The object value is greater than VHL (VHL<value).

Is_LimitsProblem

LimitsProblem

In case of dynamic limits, there is the validity mismatch of the conditions: VLL<LL<HL<VHL.



Value states

Label in the system

Predefined label

Cause

s_val_Invalid

Invalid

Invalid object value.

s_pa_Alarm

ProcAlarm

The state is occurred in case that the given object has an active process alarm.

s_pa_NoAck

NoAckPAlarm

The state is occurred in case that the process alarm is not acknowledged by operator in process D2000 HI.

s_pa_Blocked

PrAlSilent

The state is occurred in case that the given object has not any active process alarm, or Silent option is enabled at configuration of object process alarms in the process D2000 CNF.

s_val_Weak

Weak

Weak (suspicious) value is a value not valid in the system, because all the conditions of its validity are not met.

s_val_NoAck

NoAckValue

The state is occurred in case that the last object value change is not acknowledged by operator in process D2000 HI.

s_val_Transient

Transient

Transient state of the value is occurred, if the command that sets the object value was executed, but backward reading has not yet verified the value setting.