Parameters for D2000 Server
Parameters for the D2000 Server process
The process D2000 Server reads the following parameters from the system registry during its start. Values are adjusted using the process D2000 Application Manager (D2Smc.exe).
Parameter | Possible values | Meaning |
|---|---|---|
AckForValue | 0/1 | If the parameter value is 1, every new value in the system will be set to the attribute NoAckValue. Operator can acknowledge that he saw the value in the object control window. |
AlarmsWithoutFocus | 0/1 | If the value of this parameter is 1, the window opening by new alarm, don't take focus of another window of HI process |
AllowNonAdminConfLogin | 0/1 | If the value of this parameter is 1, users without administrative rights are allowed to log in to configuration processes of system D2000. Default value is 0. That means, non-administrative users can not log in to configuration processes. |
AuditDepth_RES_GROUP |
| The value different from 0 sets the full monitoring changes in the configuration of Object group. It represents a time depth of the stored information in months. The value 0 (or absence of parameter) deactivates the monitoring. |
AuditDepth_USER |
| The value different from 0 sets the full monitoring changes in the configuration of User. It represents a time depth of the stored information in months. The value 0 (or absence of parameter) deactivates the monitoring. |
APPL_NAME |
| Application name. |
AuthMethod |
| Default authentication method. The parameter can acquire the following values: Detail information about parameter is mentioned in the topic Authentication in D2000, part AuthMethod. |
AuthSecPrinc |
| Security principal for Kerberos authentication. |
BackupSysCfgDeep |
| Depth of configuration database backups that are created automatically. The backups older than defined depth are automatically deleted. It is defined in seconds. |
BackupSysCfgOffset |
| Shift of automatic backup of configuration database in given period. It is defined in the format HH:MM, i.e. shift in hours and minutes. |
BackupSysCfgPath |
| Path to directory in which the backups of configuration database, created automatically, are to be stored. Default setting is %D2000_APP%\%application_name%\SysCfg\Backup. |
BackupSysCfgPeriod |
| Period of automatic backup of configuration database. it is defined in the format NX, where N is integer and X is a time unit. The permitted time units are H - hour, D - day, W - week, M - monthe. |
ColorMandatoryItems |
| Background color for mandatory item in active pictures (Text entry field and List box). Default value = FFFFFF – i.e. no background. The color is represented by the number that can be derived from the RGB by the following formula: R + 256*G + 65536*B (see %MakeRGB function) |
ColorConditionalItems |
| Background color for conditional item in active pictures (Text entry field and List box). Default value = FFFFFF – i.e. no background. The color is represented by the number that can be derived from the RGB by the following formula: R + 256*G + 65536*B (see %MakeRGB function) |
ConfigBackUpTimeout | 0... | Maximum time [s] of backup of syscfg database. The backup is executed through the external process. |
ConfigSynchroTimeout | 0... | Maximum time [s] of synchronizing of the syscfg database. |
ControlRightForKvit | 0/1 | If the parameter value is 1, user can acknowledge an alarm only if he/she has the access right with the level Control or higher to the alarm. If the value is 0, the user needs the access level with the level Read (default state) only. |
character_encoding_APP_DEFAULT |
| Initial character encoding in the application. This parameter is used, when there is "@APP_DEFAULT@" encoding in ESL function. The initial value is "@OS_ACTUAL@". |
CheckDODMTreesInterval |
| Defines DODM tree consistency check in regular intervals. A default value is 0 (zero) in seconds. The time of next processing of the parameter value depends on the parameter value that has been set while processing it (it may be changed while the system is running):
Start Debug info, via DBG.CHECK.DODM_TREES, to see the information on the process of the DODM tree consistency check. |
CtrlAckDialog | 0/1 | Confirm setting a new value by opening a new window asking: Do you want to set the value X ? 0 - no, 1 - yes. |
CtrlCloseAfterSetValue | 0/1 | Auto close control window based on application parameter 0 - no, 1 - yes. |
descInTitleBar | 0/1 | Displaying of description in the titlebar of graphs, reports, pictures or structures instead of object name. |
dynamGraphMaxTime |
| Time length [min], that determines the range of the horizontal (time) axis of dynamic graphs. |
dynamGraphShiftTime |
| The parameter [min] determines the shift of the time axis of dynamic graphs, when drawing a graphic flow reaches the right margin of the axis. |
dynamGraphLineType | 0/1 | Definition of a graphic flow type for dynamic graphs. |
dynamGraphDescTable | 0/1 | Displaying the descriptive table of dynamic graphs. |
dynamGraphAllStatistics | 0/1 | Displaying all the graphic flows of statistic values in dynamic graphs. |
dynamGraphMultiArch | FALSE/TRUE | Opens the archive objects in multigraphs. |
dynamGraphPointer | 0/1 | Displaying the pointer on opening dynamic graphs. |
HeapArrSizeRef |
| It represents the size of auxiliary "HEAP" arrays. The parameter is set automatically when the application is started for the first time. Default value is 100 000. It enables the optimization of some bulk allocations. The settings is important especially for XML Import. The example of the log of allocated space for "HEAP" arrays is stated here. |
ExpandTree | 0/1 | If the value of the parameter is 1, then all selection windows in the system will consist complete list of logical groups (expanded). If the value is 0, then all the windows will consist list with basic logical groups only (collapsed list). |
KeepObjectValueAfterSave | 0/1 | 0 - after saving the configuration, the setting of object is "invalid" - standard behaviour - default value of parameter. |
LIC_DoNotAllowConsoleOverLimit | 0/1 | Disables to logon the console if the licence limit is exceeded. Default = off. |
LIC_DoNotAllowSysProcOverLimit | 0/1 | Disables to logon the system process if the licence limit is exceeded. Default = off. |
LIC_PostponeLicWrnToUsers | DWORD | When occurring the problem with the licence, first the administrator is informed until this time expires. After this, all users will be informed. Default value is 1 hour. The permitted maximum is the constant integer := 10*24; – [hours]. |
LogRecsLateSynchro | 0/1 | Defines CfgSynchroAuto starting - with or without parameter /NO_OBJLIFE (the object life logs are not synchronized). CfgSynchroAuto is called by D2000 Server, which is in HS state, when it receives a demand on synchronization of the configuration database from other D2000 Server connecting to a redundant group. Allowed values: |
LogTrezorPath |
| Path to the directory, where the log database depository will be created. |
LogTrezorCompressPath |
| Path to the directory for storing compressed log database depositories. |
LogTrezorCompressTime |
| Time period, during which disconnected log database depository is available for writing delayed data. The database will be compressed after expiration of this period. Value of this parameter LogTrezorPeriod must be less than the value of the parameter LogTrezorPeriod. It is given in the format NX, where N is an integer number and X gives a time unit. |
LogTrezorPeriod |
| Period for creating the log database depository. It is given in the format NX, where N is an integer number and X gives a time unit. |
MailingAddress |
| The email address to which the user can send the application error information. |
MaxMonitorItems |
| Maximal number of items, that the process D2000 Server gives to the process D2000 HI on request for the list from the log database. |
numLastUsers |
| Number of last entered users in the list of Logon dialog box of HI and GrEditor - max. 10. If the number is equal to 1, a text box displays at name. |
OEM_ProtX_Name |
| Name of OEM protocol nr.X, as will be displayed in the D2000 CNF environment. |
OEM_ProtX_DLL |
| Name of a dynamic library (.dll on Windows, .so on Linux), in which the communication protocol OEM nr.X is implemented. The name is specified without a suffix. |
OldMasks |
| Change of the format masks behaviour. |
SecurityPolicy | 0/1 | If 1 - activation of new rules, if 0 - default behaviour during a change of user's password. |
ShowConsoleUsers | 0/1 | It determines if the users of console type (*.HIP.LOG) will be displayed in the List of objects. |
SingleCommand | 0/1 | If the value of this parameter is 1, just one control window can be opened for one object at the same time in the process D2000 HI. |
SP_MinLength | 0...20 | Minimal password length. |
SP_MinLowerCaseLetters |
| Minimal count of lower case in the password. |
SP_MinNumbers | 0...10 | Minimal count of numbers in password. |
SP_MinSpecials | 0...10 | Minimal count of special symbols (e.g. ! @ # $ % ^ & a pod.) in a password. |
SP_MinUpperCaseLetters |
| Minimal count of upper case in the password. |
SP_Similarity | 0...100 | Ratio for similarity of new password to previous ones. The value can be within the interval 0...100. |
SP_History | 0...10 | Number of previous passwords, which are to be compared with new password. |
SP_AccountLockoutDuration |
| Time [s], that determines how long user's account will be blocked, when user exceeds the permitted count of logons. |
SP_AccountLockoutTreshold |
| Number of permitted invalid logons. If the number is exceeded, user's account will be blocked for the time defined by the parameter SP_AccountLockoutDuration. If the value of the parameter SP_AccountLockoutTreshold is 0, the user's account will never be blocked. |
SP_MaxConsecutiveCharacters |
| Maximum number of consecutive characters included in password. |
SP_CheckMinCharacters | 0/1 | If the value is 1 - the number of digits and non-digits in password is to be also checked. In this case, value of the parameter SP_MinNumbers defines the minimum number of both digits and non-digits. |
SrvApplHelpType | HelpFileChm | Selection of Application Help Types - NoHelp, HelpFileChm, HelpWebServerConfluence, HelpWebServerHtml, HelpSharedDir, HelpLocalApplDir, HelpLocalAnyPath |
SrvApplHelpPath |
| Set the location of the help by type SrvApplHelpType. |
SrvApplHelpMainPage |
| Default application help page. |
SrvD2000HelpType | HelpWebIPS | Selection of help types for D2000 - HelpWebIPS, HelpWebServerHtml, HelpSharedDir, HelpLocalD2000Dir, HelpLocalAnyPath |
SrvD2000HelpPath | Set the location of the help by type SrvD2000HelpType. Popis nastavenia umiestnenia závisí je vysvetlený je nižšie. | |
TCP_NO_DELAY | DEFAULT | During registration of every client connecting via TCP/IP protocol (start parameters /TP or /TPP) the process D2000 Server can change the value of the socket parameter TCP_NODELAY to TRUE/FALSE. More details are available in the description of tell command TCP_NO_DELAY. |
TestVersion |
| Color distinction of production and test server in the process D2000 HI:
Note: Parameter is implemented since the version 7.02.001. |
TNS_Service_Name |
| Configuration parameter for the configuration and log databases on Oracle platform - defines TNS of the database the configuration and log tablespaces are in. |
UseServerTimeZone | 0/1 | Allows the client processes to use the server time zone offset (KERNEL). By default, each process uses its system time zone offset. |
WinDisColorUse |
| Indication for usage the defined colour in WinDisColorValue as the color in disable wincontrols in schemes. |
WinDisColorValue |
| Colour in banned window controls in schemes (text input, buttons, trees and lists). |
XmlGitRepositoryEnabled | 0/1 | If the value is 1 and path to GIT repository is set - all changes to objects in D2000 are stored in GIT object history |
XmlGitRepositoryPath |
| Path to GIT repository where are stored all changes to objects. |
The following four parameters allow to set the logic beginning and end of day for the application. The settings have effect on the dialog boxes for defining a time interval - when you define time interval, hours and minutes are to be adjusted according to the parameters.